    Sample Boiler Calculations


    1.Convert actual steam rating into From and At 100 C

    Steam capacity from and at 100 C (212 F) is equivalent steam capacity if operating conditions are reduced to atmospheric pressure.

              

    Steam capacity = 8000 kg/hr at 10.5 kg/cm2 saturated
    Feed water inlet = 30 C
    Heat load = 8000 (664-30)  Kcal/hr
            = 5.072e06 Kcal/hr  = 20.127e06 btu/hr = 5.8976 MW

              where Sat steam enthalpy = 664 Kcal/kg
            Inlet water enthalpy  = 30 Kcal/kg
    Steam enthalpy at 100C and 1 atm pressure = 540 Kcal/kg

    Therefore, steam capacity F&A 100 C = 5.072e06/540
                                   =  9392 Kg/hr


    2. Heat Duty Calculations :

    Let us calculate heat duty of a boiler generating 50,000 kg/hr at 65 bar and 485 C
    Water inlet temperature  = 105 C

    Steam & water properties:

    Superheated steam enthalpy at 65 bar & 485 C = 808 Kcal/kg
    Saturated water enthalpy =  295 Kcal/kg

    Heat Duty     = 50000 x (808 - 105)
    = 35.15e06 Kcal/hr (139.48e06 Btu/hr or 40.87 MW)

    Usually 1 – 3% of the water flow is used for blowdown.

    Considering 2% blow down , heat in blowdown water = 50000 x 0.02 x (295 – 105)
                                      = 0.19e06 kcal/hr

    Total heat duty  = (35.15 + 0.19) e06 = 35.34e06 kcal/hr
                             =  140.24e06 Btu/hr = 41.09 MW

    In case of Hot water generator or hot water boiler,

    Heat duty = Water flow x Cp of water x Temp gain

    For example, 200,000 kg/hr of water is heated from 70 to 90 degC,

    Heat Load = 200,000 x 1 x (90-70)
             =  4.0e06 Kcal/hr
             =  15.873e06 Btu/hr or 4.651 MW

    3. Heat Transfer calculations:

    Over all heat transfer coefficient,

    Uo  = 1/(1/Ho+Rm+1/Hi*(TubeOD/TubeID)+Ro+Ri*(TubeOD/TubeID))

    Where Ho = Outside heat transfer coefficient
        Hi =  Inside heat transfer coefficient
              Rm = tube metal resistance
              Ro  =  Fouling resistance on outside tubes
              Ri  =  Fouling resistance on inside tubes

    Inside Heat Transfer coefficient can be calculated using the following correlation :

    NuInside=0.023* (ReInside^0.8)*(PrInside^0.4)

            Where NuInside = Hi x TubeID / Gas Cond

    Outside heat transfer coefficient during boiling is very high and so resistance offered is negligibly small. There are many correlations available to predict Ho, but Ho can be safely assumed to be about 10000 Kcal/hr/m2/C.

    Currently rated 3.4 by 23 people

    • Currently 3.434782/5 Stars.
    • 1
    • 2
    • 3
    • 4
    • 5

    Categories: General
    Posted by Narasimha on Friday, September 21, 2007 11:13 AM
    Permalink | Comments (6) | Post RSSRSS comment feed

    Related posts

    Comments

    Orley G. Fadriquel ph

    Sunday, June 15, 2008 8:42 AM

    Gravatar

    help. . . i need an example in the design of 10 bhp coconut shell fired water tube boiler . anybody who has the idea please send to my email add,
    i just need it very badly. . . thanks very much

    Ram babu in

    Tuesday, November 18, 2008 8:25 AM

    Gravatar

    Please send me sample calcutaion for heat transfer coefficient on shell side for condensing zone , desuperheating zone and sub cooling zone in closed feed water heater .

    vibha in

    Tuesday, November 18, 2008 3:13 PM

    Gravatar

    .just need to know how toperform the basic calculations to arrive at the design measurments of
    a water tube boiler fired by biomass fuel to generate6MW/hr at an inlet turbine input of 65ata and 495 degC.
    also need to know how to calculate the capacity of water to be boiled to acheive the above said and the other
    requirements when i use a condensing turbine.

    sarah gb

    Friday, November 21, 2008 2:33 PM

    Gravatar

    i need to know how to do basic mass and energy balances for a boiler.
    help pls!!

    Mahbub Hamid in

    Friday, December 26, 2008 10:28 AM

    Gravatar

    Interested in the calculation on coconut shell fired water tube boiler.

    ri credit repair

    Thursday, December 17, 2009 11:54 AM

    trackback

    Trackback from ri credit repair

    ri credit repair

    Comments are closed